No. Item Expected Result
4 Cable labels Both ends of each cable are labeled.
Labels are easy to understand.
5 Ground cable connection The UPS ground cable is securely
connected to the equipment room
ground bar. Use a multimeter to
measure the resistance between the
UPS ground cable and the equipment
room ground bar. The resistance is less
than 0.1 ohm.
6 Spacing between cable ties Distances between cable ties are the
same, and no burr exists.
7 Operating environment The inside and outside of the cabinet
are free from conductive dust or other
sundries.
UPSJZ-T-(1 kVA–3 kVA)
User Manual 3 Installation
2022-08-15 30