6 Storage and Maintenance
6.1 Storage
The correct way of storing the UPS is standing the UPS without unpacking in a dry
place. For a standard UPS model, charge it for 5 hours before storage. During
storage, charge and maintain it according to the following table.
Table 6-1 UPS storage
specications
Storage Temperature
Charge Interval Charging Time
–25°C to +40°C Three months 1–2 hours
40–45°C Two months 1–2 hours
6.2 Maintenance
Only qualied personnel are allowed to maintain or replace a UPS. If you need to
replace a UPS, contact your dealer.
The used batteries should be disposed of by the recycler, or they can be disposed of by the
dealer.