Specications 1 kVA 2 kVA 3 kVA
Maximum
recovery
voltage
● 290 V AC±5% (load rate: less than 80%)
● 270 V AC±5% (load rate: greater than 80%)
Input power factor (100%
resistive load)
> 0.99
Startup voltage range 120–280 V AC
Diesel generator input
capacity
Minimum: 1.5 times of the rated UPS capacity
9.4 Bypass Input Electrical Specications
Table 9-4 Bypass input electrical specications
Specications 1 kVA 2 kVA 3 kVA
Bypass voltage
range
170–264 V AC
Bypass frequency
range
47–53 Hz or 57–63 Hz
Bypass overload
capability
● 110%–120%, 30 minutes
● 120%–130%, 10 minutes
● 130%–150%, 1 minute
Input mode The mains input and bypass input share a power source.
Bypass voltage range can be set on the LCD.
9.5 Output Electrical Specications
Table 9-5 Output electrical specications
Specications
1 kVA 2 kVA 3 kVA
Rated capacity 1000 VA/800
W
2000 VA/1600
W
3000 VA/2400
W
Output power factor (PF) 0.8
Rated output voltage 200 V AC/208 V AC/220 V AC/230 V AC/240 V
AC
Output short-circuit current I
rms
: 90 A; I
peak
: 800 A
UPSJZ-T-(1 kVA–3 kVA)
User Manual 9 Technical Specications
2022-08-15 94