Alarm ID Cause ID Name Severity Clearance
Mode
Trigger
Condition
Impact
on the
System
Solution
14 1 Start
timeout
Critical This
alarm
needs to
be
manually
cleared.
The
inverter
output
voltage is
not within
±2 V of
the rated
output
voltage.
If this
alarm is
generated
when the
UPS is
running,
the UPS
transfers
to bypass
mode.
Possibl
e
cause:
The
bypass
loadin
g
capacit
y
exceed
s the
rated
load
capacit
y of
the
inverte
r.
Measu
re:
Reduce
the
output
load,
manua
lly
clear
the
alarm,
and
restart
the
UPS.
Possibl
e
cause:
An
interna
l fault
occurs.
Measu
re:
Contac
t your
dealer
or
technic
al
UPSJZ-T-(1 kVA–3 kVA)
User Manual 4 Control Panel
2022-08-15 49