Battery Routine Maintenance
Table 7-2 Battery routine maintenance
Item Expected Result Troubleshooting Maintenance
Interval
Battery
management
alarm
No battery
management
alarm is
generated.
Identify the alarm
cause based on
the alarm
information.
Monthly
Battery
appearance
1. The surface is
clean and free
of stains.
2. The battery
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from acid
leakage.
5. Batteries are
not deformed
or bulged.
If the battery
appearance is
abnormal, contact
technical support.
Monthly
Battery operating
temperature
1. The battery
ambient
temperature is
25±5°C.
2. The battery
operating
temperature
must be lower
than the
ambient
temperature
plus 20°C.
3. Battery charge
and discharge
conditions
meet the
requirements
specied in the
battery
specications.
1. Identify the
cause of the
abnormal
battery
operating
temperature.
2. If the fault
persists,
contact
technical
support.
Monthly
UPSJZ-T-(1 kVA–3 kVA)
User Manual 7 Routine Maintenance
2022-08-15 86