Valve 4 (18.9 GPM)
Operating pressure = 50 psi
32
Calibrating the Flow-Clik™ to the 
Irrigation System
Using the Flow-Clikʼs Interface Box, the sensor is 
calibrated by pressing the Calibrate button while the 
highest flow zone is operating. While the system is 
“learning” the flow, the System Status Indicator light 
will be yellow. After a 10 second period of “learning” it 
will begin to monitor system flow.
If you already know the highest flow zone within 
the system:
1.  Turn the Startup Delay dial to the 0 second position.
2.  Turn the Interrupt Period dial to the Sensor Bypass/
Calibrate position.
3.  Manually activate the zone with the highest flow.
4.  While the zone is operating, press and hold the 
Calibrate button on the Interface Box. The System 
Status Indicator light will change to yellow indicat-
ing that the sensor is being calibrated to the zone(s) 
operating. Release the calibrate button. Once the 
Flow-Clik has finished “learning” the systemʼs high 
flow zone, the light will turn to flashing green which 
means that the calibration process is complete.
5.  Turn the irrigation system off and set the Startup De
-
lay and Interrupt Period settings on the Interface Box 
(see Setting the Startup Delay and Interrupt Period).
If you do not know the highest flow zone within 
the system:
Flow Estimate Calibration Method
In some cases, you may not know the zone with the 
highest flow. A guideline that will help you easily de-
termine which zone valve has the highest flow (GPM) 
is to count the number of sprinklers on each zone. If 
there are zones with both sprays and rotors operating in 
the irrigation system, you can multiply each spray head 
by 2.0 GPM, each medium range rotor by 4.0 GPM, 
and each large range rotor by 15.0 GPM for a general 
estimate of total flow for each zone. 
For a more accurate determination of total flow for 
each zone, it is recommended that you measure the 
nozzle pressure at each sprinkler zone and then look up 
the nozzle flow at that specific pressure in the nozzle 
performance data section of the manufacturer product 
catalog. Once a determination is made of the highest 
flow zone, you can use the procedure above to calibrate 
the Flow-Clik to the system.
For example, Figure 1 shows a typical zone using I-20 
rotors. To estimate the total flow of the zone:
1.  Determine the approximate water pressure at the base 
of the sprinklers in each zone while the system is 
operating. In the illustrative example it has been deter-
mined that the sprinkler pressure in zone 4 is 50 psi.
2.  Identify the model of sprinkler and its associated 
nozzle for each valve. Valve 4 has Hunter I-20 
rotors that have various nozzles based on the dis-
tance of throw and the arc of coverage needed. For 
reference, the quantities of each type of sprinkler 
and nozzle configuration for zone 4 is identified in 
the attached irrigation legend.
3.  Determine the flow rate for each sprinkler and 
nozzle configuration. Based upon information found 
in the Hunter Catalog the associated flows for each 
Hunter I-20 sprinkler and nozzle configuration is 
listed in the attached irrigation legend.
4.  Determine the total flow of all sprinklers on the 
zone. The total flow of zone 4 in this example is 
18.9 GPM as identified in the irrigation legend.
Symbol Sprinkler Description *Flow  
@ 50 psi
Qty Total 
Flow
Hunter I-20-ADS – 1.5 1.6 x 3 = 4.8
Hunter I-20-ADS – 3.0 2.7 x 2 = 5.4
Hunter I-20-ADS – 4.0 4.2 x 1 = 4.20
Hunter I-20-ADS – .75SR .75 x 2 = 1.50
Hunter I-20-ADS – 1.5SR 1.5 x 2 = 3.0
Total Flow = 18.9 GPM
*Information obtained from the Hunter catalog, LIT-060
Figure 1 Legend
INSTALLATION INSTRUCTIONS (continued)