16 EDS 3000 IO-Link
Status: 2022-07-14 HYDAC ELECTRONIC GMBH Part no.: 669897
14.2 Setting ranges for the switching outputs
Measurement
range
Lower limit of
RP / FL
Upper limit of
SP / FH
Minimum
difference betw.
RP and SP
or FL and FH
Increment*
in bar
in bar
in bar
in bar
- 1 .. 1
-0.98
1.00
0.02
0.01
0 .. 1
0.010
1.000
0.010
0.002
0 .. 2.5
0.025
2.500
0.025
0.005
0 .. 6
0.06
6.00
0.06
0.01
0 .. 10
0.10
10.00
0.10
0.02
0 .. 16
0.20
16.00
0.20
0.05
0 .. 25
0.25
25.00
0.25
0.05
0 .. 40
0.4
40.0
0.4
0.1
0 .. 100
1.0
100.0
1.0
0.2
0 .. 250
2.5
250.0
2.5
0.5
0 .. 400
4
400
4
1
0 .. 600
6
600
6
1
0 .. 1000
10
1000
10
2
* All ranges shown in the table can be adjusted by the increments shown.
Measurement
range
Lower limit of
RP / FL
Upper limit of
SP / FH
Minimum
difference betw.
RP and SP
or FL and FH
Increment*
in psi
in psi
in psi
in psi
0 .. 15
0.15
15
0.15
0.05
0 .. 30
0.30
30
0.3
0.05
0 .. 50
0.5
50
0.5
0.1
-14 .. 75
-13.0
75
1.0
0.2
0 .. 150
1.5
150
1.5
0.5
0 .. 250
2.5
250
2.5
0.5
0 .. 500
5
500
5
1
0 .. 1000
10
1000
10
2
0 .. 3000
30
3000
30
5
0 .. 6000
60
6000
60
10
0 .. 9000
90
9000
90
20
* All ranges shown in the table can be adjusted by the increments shown.
SP = switch point
RP = switch-back point
FL = pressure window lower value
FH = pressure window upper value
14.3 Analogue output
The universal output "ou2" can be set to 4 .. 20 mA or 0 .. 10 V (corresponds to
measuring range).
Note:
If the sensor is operated in conjunction with an IO-Link master and if pin 2 is
used as an analogue output, pin 2 may not be connected with the IO-Link
master, as it does not support analogue signals.