Supply / Return Air Trunk Size CFM at .3"wc external static pressure (galvanized duct)
Round Rectangular CFM range
8"
9" 8 x 8 230-275
10" 10 x 8 275-360
11" 12 x 8 360-460
12" 14 x 8 460-570
13" 16 x 8 570-650
13" 18 x 8 650-750
14" 20 x 8 750-850
14" 22 x 8 850-950
15" 24 x 8 950-1050
Table 4 Supply air trunk size CFM at galvanized duct .3"wc ESP for return and supply air
2.3.2 Ducting installed in conditioned space
If a cooling system is connected to the unit, we recommend insulating the supply air ducting with a minimum
of 1" thick fiberglass insulation with a vapor barrier. All insulated joints must be sealed with a tape designed
for this purpose.
2.3.3 Ducting installed in un-conditioned spaces
Supply air and return air ducting should be insulated with a minimum 2" thick fiberglass insulation with a
vapor barrier. All insulated joints must be sealed with a tape designed for this purpose.
2.3.4 Making the return air openings
Both sides as well as the bottom of the unit provide markings for the maximum return air opening. Use
suitable metal cutters to perforate the marked area for the return air supply. Ensure that you cut within the
marked area.