Checking ducting connections Check
Duct insulation is installed and sealed as required.
Inspect the filter, return air ducting and registers to ensure free air movement.
Checking boiler / water heaters settings Check
Ensure the water temperature to the heating coil is sufficient to meet the heating demands of
the space.
3.2 Default settings
The following table shows the factory-default settings.
Default Settings - Basic
Heating Mode 1 stage
Cooling Mode 2 stage
Boiler Heating 1 stage and 2 stage
Temperature °F
Pump Enable On
Tankless Mode On
3.3 Default fan speed settings
For the fan speed defaults and ranges, see the table below:
AHU - Fan speed Operation
W1 Heating stage 1 = 600 CFM Range 300-800
W2 Heating stage 2 = 800 CFM Range 300 1000 (must be than heating stage 1)
Y1 Cooling stage 1 = 700 CFM Range 300 800
Y2 Cooling stage 2 = 1000 CFM Range 300-1000 (must be than cooling stage 1)
G Fan on speed = 400 CFM Range 150-1000