ifm Operating Instructions IO-Link Master with Profinet interface StandardLine 8 Ports IP 65 / IP 67 (AL1102) 2017-05-31
Appendix
>
I&M3 (Slot 0)
22781
Variable
Description
Access*
Size
Descriptor
Description of the device (ASCII, padded with spaces)
r/w
54
* ... r/w = read and write
>
I&M0 (Slot 1)
22782
Variable
Description
Access*
Size
Vendor ID
IO-Link ID of the manufacturer
r
2
OrderID
Order number of the device (numbers are separated by blanks)
r
20
Serial number
Serial number of the device (numbers separated by blanks)
r
16
Hardware revision
Hardware revision of the device
r
2
Software revision prefix
Prefix of the software revision of the device (V, R, P, U or T)
r
1
SOFTWARE_REVISION
Software revision (numbers separated by blanks, e.g. x y z in "Vx.y.z")
r
3
REVISION_COUNTER
Revision counter; is incremented with each parameter change
r
2
Profile ID
ID of the sub-module profile (Slot 1: 0x4E01 = IOLink)
r
2
Profile Specific Type
additional value for profile ID; 0, if not used
r
2
IMVersion
I&M version (default value: 0x0101)
r
2
IMSupported
Supported I&M datasets (0x0E for I&M1-3)
r
2
* ... r = only read
>
Diagnostic and alarms
22784
ECD
code
Name
Description
Type
0x02
EVNT_CODE_M_PDU_CHECK
Receive frame with CRC error
Alarm
0x1B
EVNT_CODE_S_RETRY
Repetitions detected
Alarm
0x1E
EVNT_CODE_P_SHORT
Short circuit on C/Q cable detected
Diagnostics
0x1F
EVNT_CODE_P_SENSOR
Error in the sensor supply
Diagnostics
0x20
EVNT_CODE_P_ACTOR
Error in the actuator supply
Diagnostics
0x21
EVNT_CODE_P_POWER
Error in the power supply of the IO-Link master
Diagnostics
0x28
EVNT_CODE_DSREADY_NOACTION
Data storage completed, but no action, since CRC was
correct
Alarm
0x29
DS_FAULT_IDENT
Sensor does not match the content of the data memory
Alarm
0x2A
DS_FAULT_SIZE
Sensor parameters too large for data memory
Alarm
0x2B
DS_FAULT_UPLOAD
Error during data memory transmission from the sensor
Alarm
0x2C
DS_FAULT_DOWNLOAD
Error during data memory transmission to the sensor
Alarm
0x2F
DS_FAULT_DEVICE_LOCKED
Error during data storage because the device is blocked
Alarm
0x32
EVNT_CODES_DSREADY_DOWNLOAD
Parameter transmission to the sensor finished
Alarm
0x33
EVNT_CODE_DSREADY_UPLOAD
Parameter transmission from the sensor finished
Diagnostics