Select run mode flow
↔↔
run mode temperature
• Press the Mode/Enter button for at least 2s.
■■
Setting of the detection range )
• Ensure you are in run mode flow.
• Allow the medium to flow through the system at the required maxi-
mum flow rate.
• Press the Learn/Set button for >5...<10s(= adjustment to maxi-
mum flow / upper limit of the detection range).
This setting is sufficient for the majority of waterbased applications.
Optional: adjustment to minimum flow.
• Allow the medium to flow through the system at the required mini-
mum flow rate or bring flow to a standstill.
• Press the Learn/Set button for
>10...<15s
(= adjustment to mini-
mum flow or flow standstill / lower limit of the detection range).
■■
Setting of the switch point flow (SP
Flow
)
• Ensure you are in run mode flow.
• Press the Mode/Enter button briefly.
• Press the Learn/Set button for 5s,
• keep the Learn/Set button pressed or press the button several
times until the requested switch point is set.
• Press the Mode/Enter button briefly.
■■
Monitoring excess flow
• Ensure you are in run mode flow.
• Press the Mode/Enter button twice.
• Press the Learn/Set button for 5s, release the button when LED
flashes.
• Press the Learn/Set button several times to shift the LED for the
maximum display value.
• Press the Mode/Enter button briefly.
■■
Setting of the switch point temperature (SP
Temp
)
• Ensure you are in run mode temperature.
• Press the Mode/Enter button briefly.
• Press the Learn/Set button for 5s,
• keep the Learn/Set button pressed or press the button several
times until the requested switch point is set.
• Press the Mode/Enter button briefly
27
ENGLISH
Programming