Return to factory setting
Response time flow monitoring
The typical response time of the unit is 3 ... 8 s. It can be influenced
by setting the LO-Teach and the switch point:
The lower the LO-Teach or the switch point is set, the faster the unit
switches on.
The higher the LO-Teach or switch point is set, the faster the unit
switches off.
36
Press the Learn/Set button and
keep it pressed.
The green LEDs on the right and
on the left flash,
after 5s the LED bar (green) fills
from left to right,
after a further 5 s the LED bar
(green) fills from right to left,
The indication goes off briefly.
All settings are returned to factory
setting and the unit passes into
the run mode flow.
LO HI
LO HI
HILO
LO HI
after a further 5s the LED bar
(orange) fills from left to right
(release the button as soon as the
first orange LEDs light).
LO HI
>15...<20s
M
S
M
S
Ensure you are in run mode flow.