EasyManua.ls Logo

IFM PI2797 - Switching Limit Setup; Analogue Value Scaling for OUT2

IFM PI2797
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
UK
Select [OU2] and set the function:
- [Hno] = hysteresis function/NO,
- [Hnc] = hysteresis function/NC,
- [Fno] = window function/NO,
- [Fnc] = window function/NC�
- [I] = current signal proportional to pressure 4…20 mA�
- [InEG] = current signal proportional to pressure 20…4 mA�
9.3.2 Set switching limits
Select [SP1] / [SP2] and set the value at which the output switches�
Select [rP1] / [rP2] and set the value at which the output switches back�
rPx is always smaller than SPx� The unit only accepts values which are
lower than the value for SPx�
9.3.3 Scale analogue value for OUT2
Set the minimum pressure requested in the system�
Press [Mode/Enter] until [tASP] appears�
Press [Set] and keep it pressed�
> Current setting value flashes�
Release [Set] when the display stops flashing�
> New setting value is displayed�
Press [Mode/Enter] briefly
> The current system pressure is defined as start value for the analogue
signal�
Set the maximum pressure requested in the system�
Press [Mode/Enter] until [tASP] appears�
Press [Set] and keep it pressed�
> Current setting value flashes�
Release [Set] when the display stops flashing�
> New setting value is displayed�
Press [Mode/Enter] briefly
> The current system pressure is defined as end value for the analogue
signal�
ASP/AEPcanonlybesetautomaticallywithindefinedlimits(→12.1Settingranges).
If automatic setting is carried out at an invalid pressure value, [UL] or [OL] is displayed�
After acknowledgement by [Mode/Enter] [Err] flashes, the ASP value / AEP value is not
changed�

Table of Contents

Related product manuals