EasyManua.ls Logo

Immergas EOLO STAR 24 3 E - Page 11

Immergas EOLO STAR 24 3 E
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C82
1-25
C42
C52
1-26
1-28
C82
1-27
4
6
5
1
3
2
7
8
5
9
7
A
S
11 - IE
INSTALLATORUSERTECHNICIAN
• Coupling of extension pipes and elbows. To
install snap-t extensions with other elements
of the fume extraction elements assembly, pro-
ceed as follows: Install the pipe or elbow with
the male side (smooth) on the female section
(with lip seal) to the end stop on the previously
installed element. is will ensure sealing and
joining of the elements correctly.
Figure 1-27 shows the configuration with
vertical exhaust and horizontal intake.
• Installation clearances. Figure 1-26 gives the
min. installation space dimensions of the Ø
80/80 separator terminal kit in limited condi-
tions.
Extensions for the separator kit Ø 80/80. e
max. vertical straight length (without bends)
that can be used for Ø 80 intake and exhaust
pipes is 41 metres of which 40 intake and 1
exhaust. The total length corresponds to a
resistance factor of 100. e total usable length
obtained by adding the length of the intake and
exhaust pipes Ø 80 must not exceed the values
stated in the following table. If mixed accessori-
es or components are used (e.g. changing from
a separator Ø 80/80 to a concentric pipe), the
maximum extension can be calculated by using
a resistance factor for each component or the
equivalent length. e sum of these resistance
factors must not exceed 100.
• Temperature loss in fume ducts. To prevent
problems of fume condensate in the exhaust
pipe Ø 80, due to fume cooling through the
wall, the length of the pipe must be limited to
just 5 m. Fig. 1-28). If longer distances must
be covered, use Ø 80 pipes with insulation (see
insulated separator kit Ø 80/80 chapter).
N.B.: when installing the Ø 80 ducts, a section
clamp with pin must be installed every 3 metres.
* e air intake pipe can be increased to 2.5
metres if the exhaust bend is eliminated, 2
metres if the air intake bend is eliminated, and
4.5 metres eliminating both bends.
e kit includes:
N°1 - Exhaust gasket (1)
N°1 - Female intake ange (3)
N°1 - Flange gasket (2)
N°1 - Female exhaust ange (4)
N°2 - 90° bend Ø 80 (5)
N°1 - Intake terminal Ø 80 (6)
N°2 - Internal white wall sealing plates (7)
N°1 - External grey wall sealing ring (8)
N°1 - Exhaust pipe Ø 80 (9)
Maximum usable length
(including intake terminal with grill and two 90° bends)
NON INSULATED PIPE INSULATED PIPE
Exhaust (m) Intake (m) Exhaust (m) Intake (m)
1 36,0* 6 29,5*
2 34,5* 7 28,0*
3 33,0* 8 26,5*
4 32,0* 9 25,5*
5 30,5* 10 24,0*
* e air intake pipe can be increased to 2.5 metres if the exhaust bend is
eliminated, 2 metres if the air intake bend is eliminated, and 4.5 metres
eliminating both bends.
11 22,5*
12 21,5*
Important: the boiler was designed to evacuate
combustion product up to a maximum extension
of 27 linear m to the exhaust, with 1 m plus 90°
bend at intake. If installation requires an exten-
sion of the ue ttings up to the exhaust that
exceeds the 12 m recommended, it is necessary
to properly consider the possibility that conden-
sation may form inside the duct and therefore
Immergas “Serie Blu” insulated ue ttings, or
other ue ttings with similar characteristics,
should be used.

Other manuals for Immergas EOLO STAR 24 3 E

Related product manuals