8
INSTALLER
USER
MAINTENANCE TECHNICIAN
TECHNICAL DATA
e hex head screws supplied in the blister pack are
to be used exclusively to x the relative mounting
bracket to the wall
ese boilers are used to heat water to below boiling
temperature in atmospheric pressure.
ey must be connected to a central heating system
and domestic hot water circuit suited to their perfor-
mance and capacity.
ey cannot be connected directly to low-temperature
systems.
Risk of damage due to corrosion caused by unsuit-
able combustion air and environment.
Spray, solvents, chlorine-based detergents, paints,
glue, ammonium compounds, powders and similar
cause product and ue duct corrosion.
- Check that combustion air power supply is free from chlorine,
sulphur, powders, etc.
- Make sure that no chemical substances are stored in the place
of installation.
- If you want to install the product in beauty salons, paint
workshops, carpenters shop, cleaning companies or
similar, choose a separate installation area that ensures
combustion air supply that is free from chemical substances.
- Make sure the combustion air is not fed from chimneys that
were used with gas boilers or other heating devices. In fact,
these may cause an accumulation of soot in the chimney.
ATTENTION:
- Type B open chamber boilers must
not be installed in places where com-
mercial, artisan or industrial activities take
place, which use products that may develop
volatile vapours or substances (e.g. acid
vapours, glues, paints, solvents, combusti-
bles, etc.), as well as dusts (e.g. dust deriv-
ing from the working of wood, coal nes,
cement, etc.), which may be harmful for the
components of the appliance and jeopardise
operation.
- in B
22
conguration, unless otherwise pro-
vided for by local regulations in force: the
boilers must not be installed in bedrooms,
bathrooms or bedsits. ey must neither be
installed in rooms containing solid fuel heat
generators nor in rooms communicating
with said rooms.
- e installation rooms must be permanently
ventilated, in compliance with the local reg-
ulations in force (at least 6 cm
2
for every kW
of installed heat input, except in the event of
any increases needed for electro-mechanical
vacuum cleaners or other devices that could
put the installation room under vacuum).
- e installation of appliances in B
22
cong-
uration is only recommended in places that
are not lived in and which are permanently
ventilated.
ATTENTION:
Failure to comply with the above implies
personal responsibility and invalidates
the warranty.