1.15 CONCENTRIC VERTICAL KIT
INSTALLATION.
Type C configuration, sealed chamber and
fan assisted.
Concentric vertical intake and exhaust kit. is
vertical terminal is connected directly to the out-
side of the building for air intake and ue exhaust.
N.B.: the vertical kit with aluminium tile en-
ables installation on terraces and roofs with a
maximum slope of 45% (approx. 25°) and the
height between the terminal cap and half-shell
(260 mm) must always be observed.
Vertical kit with aluminium tile 80/125 Ø.
Kit assembly (Fig. 1-13): Install the 80/125 Ø
adapter (1) on the central hole of the boiler fully
home. Slide the gasket (2) along the adapter (1)
up to the relevant groove, Fix it to the lid using
the previously disassembled sheet steel plate (3)
Installation of the fake aluminium tile: replace
the tiles with the aluminium sheet (5), shaping
it to ensure that rainwater runs o. Position the
xed half-shell (6) on the aluminium tile and
insert the intake-exhaust pipe (7). Fit the 80/125
Ø concentric terminal pipe with the male end
(6) (smooth) to the female end of the adapter
(1) (with lip gasket) up to the stop; making sure
that the wall sealing plate (4) has been tted, this
will ensure sealing and joining of the elements
making up the kit.
• Maximum length (MAX L) (Fig. 1-13). e kit
with this conguration can be extended up to
a max. measurement of 15.0 m with Victrix Pro
80 2ErP, 11.0 m with Victrix Pro 100 2ErP and
6.0 m with Victrix Pro 120 2ErP, including the
terminal.
e kit includes:
1 - Adaptor 80/125 Ø (1)
1 - Gasket (2)
1 - Ring (4)
1 - Aluminium tile (5)
1 - Fixed half-shell (6)
1 - Int./exhaust concentric terminal
80/125 Ø (7)
1 - Mobile half-shell (8)