3.27 TECHNICAL DATA.
- Flue temperature values refer to an air inlet
temperature of 15°C and ow temperature of
50°C.
- The maximum sound level emitted during
boiler operation is < 55dBA. e sound level
value is referred to semianechoic chamber tests
with boiler operating at max. heat output, with
extension of ue gas exhaust system according
to product standards.
Victrix Pro 80 2ErP Victrix Pro 100 2ErP Victrix Pro 120 2ErP
Nominal heat input kW (kcal/h) 75.3 (64722) 92.3 (79385) 114.1 (98109)
Minimum heat input kW (kcal/h) 7.6 (6532) 9.8 (8401) 11.4 (9813)
Nominal heat output (useful) kW (kcal/h) 73.0 (62780) 90.0 (77400) 111.0 ( 95460)
Minimum heat output (useful) kW (kcal/h) 7.2 (6192) 9.4 (8084) 11.0 (9460)
Eective thermal eciency 80/60 Nom./Min. % 97.0 / 94.8 97.5 / 96.2 97.3 / 96.4
Eective thermal eciency 50/30 Nom./Min. % 106.6 / 106.9 107.0 / 107.4 106.7 / 107.2
Eective thermal eciency 40/30 Nom./Min. % 107.3 / 107.2 107.4 / 107.6 107.2 / 107.5
Heat loss at casing with burner On/O (80-60°C) % 0.34 / 0.80 0.41 / 0.60 0.28 / 0.70
Heat loss at ue with burner On/O (80-60°C) % 0.01 / 2.2 0.01 / 1.9 0.01 / 2.0
Central heating circuit max. operating pressure bar 4.4 4.4 4.4
Central heating circuit max. operating temperature °C 90 90 90
Adjustable central heating temperature °C 20 - 85 20 - 85 20 - 85
Head available with 1000 l/h ow rate kPa (m H
2
O) 81.4 (8.30) 116.5 (11.88) 116.5 (11.88)
Weight of full boiler kg 85.0 106.0 114.2
Weight of empty boiler kg 81.0 95.9 102.5
Boiler water content l 4.0 10.1 11.7
Electrical connection V/Hz 230/50 230/50 230/50
Nominal absorption A 1.5 2.3 2.5
Installed electric output W 195 345 385
Pump consumption W 82 183 186
Fan power consumption W 100 154 184
Equipment electrical system protection - IPX5D IPX5D IPX5D
Max. operating room temperature °C +50 +50 +50
Min. operating room temperature °C -5 -5 -5
Min. operating room temperature with anti-freeze kit
(Optional)
°C -15 -15 -15
Flue gas max. temperature °C 75
75 75
NO
X
class -
6
6 6
Weighted NO
X
mg/kWh 25.0 20.0 33.0
Weighted CO mg/kWh 16.0 12.0 18.0
Type of appliance C13 / C33 / C63 / B23p / B33 / B53p
Category II2H3P