34
INSTALLERUSER
MAINTENANCE TECHNICIAN
Programming menu
Menu item Description Adjustment range Default value
Customised
Value
P26 Min fan Speed
is denes the min fan speed and therefore the minimum
relative boiler operating power (RPM speed is calculated by
multiplying the value displayed by 50)
0 ÷ P25 RPM x 50
80 kW Met. 27
80 kW LPG 25
100 kW Met. 26
100 kW LPG 25
120 kW Met. 26
120 kW LPG 25
P27 Min pump speed
Denes the minimum pump speed in heating mode at the
minimum boiler power. Attention: do not go below 30%
1 ÷ 100 % 30 %
P28
Pump speed
during burner
ignition
Denes the minimum pump speed in heating mode when the
burner turns on
Attention: do not go below 40%
1 ÷ 100 % 40 %
P29
DHW
conguration
is is used to select the DHW operating mode, choosing
between NTC probe or on/o thermostat
1 = NTC probe
17 = on/o
thermostat
1
P30
Speed during fan
power-on
is denes the fan speed during burner ignition
Attention: do not change this parameter (RPM speed is
calculated by multiplying the value displayed by 50)
0 ÷ 114 RPM x 50
(range limited by
parameters P25
and P26)
46
P31
Unit of
measurement
is denes the unit of measure on the display, whether
metric or Imperial
0 ÷ 127 = °C - kW
128 ÷ 256 = °F -
kBTu/h
0
P32 Set Resc Min
Limits the minimum value of the heating set. (e parameter
takes priority in relation to the value set from the pushbutton
panel)
P33
Antifreeze
function activated
by the common
ow probe
It activates the antifreeze function launched by the common
ow probe. e boiler turns on once there is a drop below the
set value
2 ÷ 20 °C 5°C
P34
Antifreeze
function
deactivated by
the common ow
probe
It deactivates the antifreeze function launched by the
common ow probe. e boiler turns o once the set
temperature is reached
2 ÷ 20 °C 15°C
P35
Delayed
Activation /
Deactivation of
the second boiler
With its simple cascade operation, it avoids unnecessarily
turning the second boiler on and o
0 ÷ 255 seconds 60 seconds
P36
Temperature
adjustment
calculation time
is denes the time interval required to calculate the boiler
temperature
Attention: do not change this parameter
1 ÷ 10 seconds 3 seconds
P37 0 ÷ 10 V inlet
It denes whether the boiler must function with the
temperature or probe set0 = temperature set
1 = power set
P38
Common
ow probe
conguration
It activates the common ow probe functioning
0 = no probe
1 = probe present