EasyManua.ls Logo

Immergas Victrix Pro 80 2ErP - Page 42

Immergas Victrix Pro 80 2ErP
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
INSTALLERUSER
MAINTENANCE TECHNICIAN
Victrix Pro 120 2ErP.
METHANE (G20) PROPANE (G31)
HEAT OUTPUT HEAT OUTPUT
BURNER GAS FLOW
RATE
REVS
FAN
BURNER GAS FLOW
RATE
REVS
FAN
(kW) (kcal/h) (m
3
/h) (n°) (kg/h) (n°)
111.0 95460 12.07 7000 8.86 7000
108.0 92880 11.74 6810 8.62 6800
105.0 90300 11.41 6620 8.37 6600
102.0 87720 11.08 6430 8.13 6400
99.0 85140 10.75 6240 7.89 6200
96.0 82560 10.42 6050 7.65 6010
93.0 79980 10.09 5870 7.40 5810
90.0 77400 9.76 5680 7.16 5620
87.0 74820 9.43 5500 6.92 5440
84.0 72240 9.10 5320 6.68 5250
81.0 69660 8.78 5140 6.44 5070
78.0 67080 8.45 4970 6.20 4880
75.0 64500 8.13 4790 5.97 4700
72.0 61920 7.80 4620 5.73 4530
69.0 59340 7.48 4440 5.49 4350
66.0 56760 7.15 4270 5.25 4170
63.0 54180 6.83 4100 5.01 4000
60.0 51600 6.51 3930 4.78 3830
57.0 49020 6.18 3760 4.54 3660
54.0 46440 5.86 3590 4.30 3490
51.0 43860 5.54 3430 4.06 3330
48.0 41280 5.21 3260 3.83 3160
45.0 38700 4.89 3100 3.59 3000
42.0 36120 4.57 2930 3.35 2840
39.0 33540 4.24 2770 3.12 2680
36.0 30960 3.92 2610 2.88 2520
33.0 28380 3.60 2450 2.64 2360
30.0 25800 3.27 2290 2.40 2200
27.0 23220 2.95 2130 2.16 2050
24.0 20640 2.62 1970 1.92 1900
21.0 18060 2.30 1820 1.69 1750
18.0 15480 1.97 1660 1.45 1600
15.0 12900 1.64 1510 1.21 1450
12.0 10320 1.32 1350 0.97 1300
11.0 9460 1.21 1300 0.89 1250
N.B.
- e power data provided in the table is ob-
tained with 0.5 m long intake/exhaust pipe.
- Gas ow rates refer to heating output below a
temperature of 15°C and pressure of 1013 mbar.
- Burner pressure values refer to use of gas at
15°C.
- e number of revs for the fan on the display
is expressed in revs / 50 (Ex.: 1000 revs = 20).