EasyManua.ls Logo

Immergas VICTRIX TERA 24 PLUS - Page 35

Immergas VICTRIX TERA 24 PLUS
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
INSTALLERUSERMAINTENANCE TECHNICIAN
Id
Parameter
Parameter Description Range Default
Customised
value
A0 Hydraulic model Denes the type of hydraulics in the boiler (0 = instant; 1 = storage tank) 0 ÷ 1 0
A1
Maximum pump
speed
Denes the maximum operating speed of the circulator
(If A1 = A2 circulator operating at set speed)
A2 - 9 9
A2
Minimum pump
speed
Denes the minimum operating speed of the circulator 1 - A1 6
A3
Pump operating
mode
Sets the pump operating mode
- DELTA T = 0: proportional head (see Parag. 1.28)
- DELTA T = 5 ÷ 25 K: T constant (see Parag. 1.28)
0 ÷ 25 15
A4
Storage tank ow
oset
Establishes the temperature to be added to the DHW set-point to calculate
the ow set to heat the storage tank (only useful with a coupled storage tank
and parameter A0=1).
5 ÷ 50 °C 25
A5
Storage tank
activation oset
Temperature value to be subtracted from the DHW set-point to calculate the
boiler ignition to heat the storage tank (only useful with a coupled storage
tank and parameter A0=1).
0 ÷ 15 °C 3
A6 DHW thermostat
Establishes the switch-o method in DHW mode.
0 Fixed: the switch-o temperature is xed at the maximum value regardless
of the value set on the control panel.
1 Correlated: the boiler switches o according to the temperature set.
0 ÷ 1 0
Id
Parameter
Parameter Description Range Default
Customised
value
S0
DHW minimum
no. of fan revs
Denes the operating speed of the fan at minimum DHW output
20 ÷ 60
(x 50 =RPM)
28 (G20)
27 (G31)
S1
DHW maximum
no. of fan revs
Denes the operating speed of the fan at maximum DHW output
S0 ÷ 140
(x 50 =RPM)
121 (G20)
115 (G31)
S2
Ignition phase
no. of fan revs
Denes the operating speed of the fan during the ignition phase
40 ÷ 80
(x 50 =RPM)
56 (G20)
56 (G31)
Attention: check the serial number on the boiler.
From number 7211394 use the data in the following table.
Id
Parameter
Parameter Description Range Default
Customised
value
S0
DHW minimum
no. of fan revs
Denes the operating speed of the fan at minimum DHW output
20 ÷ 60
(x 50 =RPM)
27 (G20)
26 (G31)
S1
DHW maximum
no. of fan revs
Denes the operating speed of the fan at maximum DHW output
S0 ÷ 140
(x 50 =RPM)
121 (G20)
115 (G31)
S2
Ignition phase
no. of fan revs
Denes the operating speed of the fan during the ignition phase
40 ÷ 80
(x 50 =RPM)
56 (G20)
56 (G31)

Table of Contents

Related product manuals