STZSkW ed 12/07 ZEUS Superior kW
Technical DocumentationTechnical Documentation
M5 Menu (CONFIG)
(an access code must be introduced)
1st Level 2nd Level Options Description Default value
Value set by
the technician
P51
(MEAS.PASC.)
Displays the value of the fan signal read by the circuit board - -
P52
(SET PASC.)
Sets the fan reference set during its normal functioning
(can be set from 60Pa to 90Pa)
Set in the
factory during
inspection
P53
(POWER)
24 KW
(24 KWSET)
Identies the power of the boiler on which the circuit board is installed
Equal to
boiler power
Equal to boiler
power
28 KW
(28 KWSET)
32 KW
(32 KWSET)
P54
(DHWT.)
P54.1
(DHW NTC1)
Displays the temperature measured by the domestic hot water probe
positioned on the storage tank.
- -
P54.2
(DHW NTC2)
Not used on this model - -
P55
(CALCCHT)
Displays the heating ow temperature at which the boiler operates,
calculated by the active controls on system heat adjustment
- -
SERVICE
(BOIL.PAR.)
P56
(GAS TYPE)
G20
(METHANE)
e boiler operates with methane gas
Equal to the
type of gas
in use
GPL
(LPG)
e boiler operates with LPG gas
G110
(G110)
e boiler operates with G110 gas
P58
(MAX DHW)
0% ÷ 100%
Sets the maximum power in domestic hot water mode
(can be set from 0% to 100%)
100%
P59
(MAX CH)
0% ÷ 100% Sets the maximum power in room heating mode 100%
P60
(MIN DHW)
0% ÷ 60% Sets the minimum power in domestic hot water mode 0%
P61
(MIN CH)
0% ÷ 60% Sets the maximum power in room heating mode 0%
P66
(T.REG.
PAR.)
P66/A
(MIN. CH T.)
Without external probe (Optional) denes the minimum ow tempe-
rature. With the external probe present, it denes the minimum ow
temperature corresponding to operations with maximum external
temperature.
(can be set from 35°C to 50°C)
N.B.: the parameter must be conrmed in order to continue (press “D
or exit from “P66” regulation by pressing“C”)
35°C
P66/B
(MAX. CH
T.)
Without external probe(Optional) enes the maximum ow tempe-
rature. With the external probe present, it denes the maximum ow
temperature corresponding to operations with minimum external
temperature
(can be set from 50°C to 85°C)
N.B.: the parameter must be conrmed in order to continue (press “D
or exit from “P66” regulation by pressing “C”)
85°C
P66/C
(MIN. EXT
T.)
With external probe present it denes at which minimum external
temperature the boiler must operate at maximum ow temperature
(adjustable from -20°C to 0°C)
N.B.: the parameter must be conrmed in order to continue (press “D
or exit from “P66” regulation by pressing “C”)
-5°C
P66/D
(MAX. EXT
T.)
With external probe present it denes at which maximum external
temperature the boiler must operate at minimum ow temperature
(adjustable from 5°C to +25°C)
N.B.: the parameter must be conrmed in order to continue (press “D
or exit from “P66” regulation by pressing “C”
25°C
Menu congurations M5 (CONFIG). is menu contains
all conguration options of the booiler functioning parame-
ters. (e rst entry of the various options that appears inside the
parameter is that selected by default).