Tethered Remote Calibration Mode
To enter the calibration mode on the tethered remote control,
1 Turn on the CRANE switch.
2 With the trigger released, hold the momentary EXTENSION OUT and WINCH UP switches
while activating the momentary LOWER DOWN switch four (4) times in succession.
3 The CRANE AND COMPRESSOR ON output and LED will begin to flash, indicating
successful entry to the calibration mode. Release momentary switches at this time.
4 Use the CCW/CW momentary switches to adjust the minimum output to the valve. CCW will
increase the minimum output and CW will decrease the minimum output.
5 To adjust the maximum output to the valve, squeeze the trigger all the way and use the
CCW/CW switches in a similar manner. CCW will increase the maximum output and CW will
decrease the maximum output.
6 When finished, move the CRANE switch to the OFF position to save the new values to flash
memory and exit the calibration mode.