EasyManua.ls Logo

INFOSEC UPS SYSTEM E4 Evolution II TT Series - Page 133

INFOSEC UPS SYSTEM E4 Evolution II TT Series
141 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
132
INFOSEC UPS SYSTEM 15, Rue du Moulin 44880 Sautron France www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 fax : +33(0)2 40 94 29 51 hotline@infosec.fr 02 19 AA 59 203 07
UPS stay in Bypass mode and No AC input is indicated.
Step 2: Switch OFF the external power switch to disconnect the AC power to the UPS. Wait until the LCD
is OFF.
Step 3: Switch OFF the battery breaker if the UPS will disconnect from the AC power for a long time.
6-4-2. Turn Off Operation in Line Mode
The LCD diagrams are shown below when the UPS operates in the Line Mode.
Step 1: Press “POWER” button for 2 seconds to turn off the UPS. Or use the Menu-Control-System Turn
Off to turn off the UPS.
After turning off, the UPS will tranfer to Standby Mode or Bypass Mode, depending on the “Bypass Mode”
Setting.
6-4-3. Turn Off Operation in Battery Mode
The LCD diagram is shown below when the UPS operates in the Battery Mode.

Table of Contents

Related product manuals