6-3. Maintenance Bypass Operation
If any fault occurs on any one of power stages/modules, please follow below steps to transfer to
maintenance bypass for maintenance and UPS protection as below.
6-3-1. Transfer to maintenance bypass
Step 1:
Remove the mechanical lock plate of maintenance bypass.
E4 Evolution II 100K/120K TT S
E4 Evolution II 160K/200K TT S
Step 2
Make sure the UPS operates in Bypass mode as shown below.
Step 3
Switch ON the maintenance bypass breaker as shown below.
E4 Evolution II 100K/120K TT S
E4 Evolution II 160K/200K TT S