- 123 -
SB3:Reverse rotation button
Dln is multifunctional input terminals of DI1 to DI5 (DI1 to DI10 if
multifunctional input and output expansion card is selected). In this way, it
shall define the corresponding terminal functions as No.3 function “Three-line
Mode Running Control".
3: Three-line running mode 2: In this mode, Dln is enabled terminal, and the
running command is given by FWD, while the direction is determined by the
status of REV.
Stop command is performed through disconnecting the DIn signal.
Fig.6-7 Three-line Running Mode
Where,
SB1: Stop button
SB2: Running button
Dln is multifunctional input terminals of DI1 to DI5 (DI1 to DI10 if
multifunctional input and output expansion card is selected). In this way, it
shall define the corresponding terminal functions as No.3 function “Three-line
Mode running Control".
Terminal
UP/DOWN Speed
Factory default
value
1.00Hz/s
F4-17
Setup
range
0.01Hz/s~100.00Hz/s
Terminals UP/DOWN is used to adjust the change rate when setting the
frequency.
AI1 minimum
input
Factory default
value
0.02V
F4-18
Setup
range
-11.00V~11.00V
AI1 minimum
input
corresponding
setup
Factory default
value
0.0%
F4-19
Setup
range
-100.00%~100.0%
K Running Direction Selection
0 Forward Rotation
1 Reverse Rotation
IS300
FWD
DIn
REV
COM
SB2
SB1
K