- 144 -
Forward/reverse
rotation dead-zone
time
Factory
default value
0.00s
F8-12
Setup range 0.00s~ 3000.0s
During the setting of forward/reverse rotation of the driver, the transition time
at the output zero frequency position is shown in the following figure:
Fig.6-11 Schematic diagram for Forward/ Reverse Rotation Dead-zone Time
Reverse control Factory default value 0
0
Reverse rotation enabled
F8-13
Setup range
1 Reverse rotation inenabled
When this parameter is set to 0, it can perform reverse rotation control on the
driver with the keyboard, terminal or communication.
When this parameter is set to 1, the reverse rotation control function is
enabled and has nothing to with the command source selection. That is to
say, the reverse control function is inenabled at the time of keyboard,
terminal and communication controls.
Setup frequency lower
than frequency lower
limit action
Factory default
value
0
0 Run with frequency lower limit
1 stop
F8-14
Setup
range
2 Running with zero speed
It is used to select the running status of the driver when the setup frequency
is lower than the frequency lower limit.
In order to avoid that the motor always runs with low speed, it can use this
function to stop.
Output Frequency
Forward Rotation
Reverse Rotation
Dead Zone Time
RUNNING
TIME