- 151 -
Fault auto reset
times
Factory default
value
0
F9-09
Setup range
0 to 3
When the driver selects fault auto
reset, it is used to set the times of
auto reset. If this value is
exceeded, the driver will stop
because of failure and wait for
maintenance.
Fault rely action selection
during the fault auto reset
Factory
default value
1
F9-10
Setup range
0: No action
1: Action
After the failure auto reset function
is selected, this parameter can be
set to determine if it needs the
action of the faulty relay so as to
shield the fault alarm caused and
ensure the continuous operation of
the equipment during the failure
reset.
Fault auto reset
interval
Factory default value 1.0s
F9-11
Setup range
0.1s ~ 100.0s
The waiting time of the driver from
the fault alarm to auto reset.
Input phase loss
protection selection
Factory default value 1
F9-12
Setup
range
0: Inenabled
1: Enabled
Select whether to provide
protection for input phase loss.
Only the MD series driver of G
model with over 18.5kW can have
input phase loss protection
function, and the P model with
18.5kW has not such function no
matter whether F9-10 is set to 0 or
1.
Output phase loss
protection selection
Factory default value 1
F9-13
Setup
range
0: Inenabled
1: Enabled
Select whether to provide
protection for output phase failure.