- 93 -
System oil
pressure
Factory default
value
175.0kg/cm
2
A3-02
Setup
range
0.0kg/cm
2
to maximum oil pressure(A3-03)
Set the system maximum oil pressure value.
Maximum oil
pressure
Factory default
value
250.0kg/cm
2
A3-03
Setup
range
System oil pressureA3-02 to 500.0kg/cm
2
Set the pressure scale of the oil pressure sensor. (Corresponding
voltage DC010V output pressure sensor)
Oil pressure
command
risetime
Factory default
value
20ms
A3-04
Setup
range
0ms2000ms
Corresponding filter time of oil pressure command
Oil pressure
control Kp1
Factory default
value
210.0
A3-05
Setup
range
0.0800.0
The Oil pressure controls PID proportional gain of the first group. The greater setup
value is, the faster responses will be.Responding too fast that can easily lead to overshoot
and cause system instability and running oscillation. The smaller setting value is, the slower
response will be, responding too slow can easily lead to inefficient and product instability.
Oil pressure
control Ti1
Factory default
value
0.100s
A3-06
Setup
range
0.001s10.000s
The oil pressure controls PID integration time of the first group. The
smaller setup value is, the faster response will be.Responding too fast that
can easily lead to overshoot, cause system instability and running oscillation.
The greater setup value is, the slower response will be, responding too slow
can easily lead to inefficient and product instability.