MD021 Plastic Wire Drawing Machine User Manual 
 
Set the parameters based on the parameters on the nameplate of 
the motor. 
To  guarantee  the  control  performance,  choose  the  standard 
adaptive  motor  of  the  inverter.  If  a  great  difference  exists 
between the actual motor power and the adaptive motor power, 
the control performance of the inverter may degrade. 
 
Cutoff 
frequency  of 
torque boost 
0.01  Hz  to 
maximum 
frequency (F0-02) 
 
To compensate the low frequency torque characteristics of V/F control, 
you can boost the output voltage of the inverter at low frequency. 
"Torque boost" (F0-10) is set to a certain percentage of the input rated 
voltage of the inverter. The setting is as follows: 
When this parameter is set to 0.0%, automatic torque boost is applied 
for the inverter. 
Set this parameter to a larger value for a low-power motor and to a 
smaller value for a high-power motor. 
If this parameter is set to a too large value, the motor may easily be 
overheated and the inverter may suffer over-current.