17
CONTINUE
Para.
Parameter name Default
Commissioning
Select command source
F0-
02
Command source selection 1 0
Perform motor auto tuning
F1-
37
Auto-tuning selection 0 3
0: No auto-tuning
2: Asynchronous motor dynamic auto-tuning
3: Asynchronous motor static auto-tuning(NEW)
NOTE
Steps of auto-tuning:
1. Make sure the UVW connection between inverter and
motor is not cut off by output contactor; if it is cut off,
then manually handle with the output contactor;
3. Set F1-37=3, press
4. Press the key on panel, then motor starts auto-tuning, it usually takes about 30 seconds to finish
this auto-
5. Restore F0-02 to the default value 1.
Select Control mode
F0-
01
Control mode selection 2 0 or 2
0: SVC control
2: VF control
Select
frequency reference source
F0-
03
Main frequency source X selection 6 2 or 6
0:Digital setting F0-08(pressing or can change F0-
08 easily, and the changed
1:Digital setting F0-08(pressing or can change F0-08 easily, but changed
value would be cleared after power off)
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference setting
7: Simple PLC
8: PID
9: Communication setting
Set AI if AI is frequency
reference
F4-
13
AI curve 1 minimum input 0.00 0.00
0 V to F4-15;
F4-
14
Corresponding setting of AI1minimum input
0.0 0.0
-100.0% to 100.0%
F4-
15
AI1 maximum input 5.00
F4-13 to 10.00 V
F4-
16
Corresponding setting of AI1maximum input
100.0
-100.0% to 100.0%
CONTINUE
Para.
Parameter name Default
Commissioning

Related product manuals