Para.
Parameter name Default
Commissioning
Set multi-reference values
FC-
01
Reference 1 100.0 100.00
if multi
-
reference is frequency reference
0.0 to 100.0%.
NOTE: FC-01 is set as nominal speed of elevator.
FC-
02
Reference 1 11.0 11.0
0.0 to 100.0%.
NOTE: FC-02 is set as creep speed of elevator.
FC-
04
Reference 4 40.0 40.00
0.0 to 100.0%.
NOTE: FC-04 is set as inspection speed of elevator.
FC-
0
8
Reference 8 20.0 20.0
0.0 to 100.0%.
NOTE: FC-08 is set as ARD speed of elevator.
Set DI function
F4-
00
DI1 function selection 1 1 (Forward run)
0: No function
1: Forward RUN (FWD)
2: Reverse RUN (REV)
8: IGBT Enable
9: Fault reset (RESET)
12: Multi-reference terminal 1
13: Multi-reference terminal 2
14: Multi-reference terminal 3
Setting range:0 to 59;
NOTE: this signal comes from elevator controller.
F4-
01
DI2 function selection 2 2 (Reverse
run)
Setting range same as DI1;
NOTE: this signal comes from elevator controller.
F4-
02
DI3 function selection 12 12
Setting range same as DI1
NOTE: if analog input is used as frequency reference, then DI3 is useless, just leave it alone. If multi-
F4-
03
DI4 function selection 13 13
Setting range same as DI1.
NOTE: if analog input is used as frequency reference, then DI4 is useless, just leave it alone. If multi-
F4-
04
DI5 function selection 14 14
setting range same as DI1;
NOTE: if analog input is used as frequency reference, then DI5 is useless, just leave it alone. If multi-
F4-
05
DI6 function selection 0
setting range same as DI1;
CONTINUE
Para.
Parameter name Default
Commissioning