Para.
Parameter name Default
Commissioning
Set DO function
F5-
01
FM function selection 2 2(Fault output)
0 : No output
1 : AC Drive running
2 : Fault output
36: Software current exceeding limit
42 : Brake output
43 : MC (Magnetic contactor) output
Setting range:0 to 59;
NOTE: this signal goes to magnetic contactor.
F5-
02
Relay function selection(TA/TB/TC) 43 43 (MC)
Setting range same as FM;
NOTE: this signal goes to magnetic controller.
F5-
0
3
Relay function selection(PA/PB/PC) 42 42(Brake)
Setting range same as FM;
NOTE: this signal goes to brake contactor.
Set magnetic contactor
F8-
60
Drive run delay ON set time 0.20 0.20
0.00 to 10.00 Sec;
NOTE: if MC is controlled by elevator controller, then F8-60 is useless.
F8-
61
MC contactor delay OFF set time 0.20 0.20
0.00 to 10.00 Sec;
NOTE: if MC is controlled by elevator controller, then F8-61 is useless.
Set brake contactor
F8-
55
Brake release current threshold 5 5
0 to 200%;
F8-
56
Brake release frequency threshold 0.00 0.0
0.00 to 25.00 Hz;
F8-
57
Brake release delay ON set time 0.0 0.0
0.0 to 5.0 Sec;
F8-
58
Brake apply frequency threshold 0.5 0.5
0.00 to 25.00 Hz;
F8-
59
Brake apply delay OFF set time 0.2 0.2
0.0 to 5.0 Sec;
Set acceleration and deceleration
F0-
17
Acceleration time 1 3.0 3.0
0.0 to 6500.0 sec.
F0-
18
Deceleration time 1 2.0 2.0
0.0 to 6500.0 sec.
Set startup frequency
F6-
03
Startup frequency 1.0 1.0
0.0 to 10.0 Hz;
F6-
04
Startup frequency active set time 0.3 0.3
0.0 to 100.0 Sec
CONTINUE
Para.
Parameter name Default
Commissioning