Three-phase 200 V to 240 V
Table 7–8 Electrical specifications (three‑phase 200 V to 240 V) (T1 to T2 models)
Item
Specifications
Model: MD500‑2Txxxxx‑PLUS
0.4G/
0.7PB
0.7G/
1.1PB
1.1G/1.5PB 1.5G/2.2PB 2.2G/3.7PB
3.7G/
5.5PB
Structure T1 T2
Output
Power (kW) (heavy load)
0.4 0.75 1.1 1.5 2.2 3.7
Power (kW) (light load)
0.75 1.1 1.5 2.2 3.7 5.5
Rated output current (A)
(heavy load)
2.1 3.8 5.1 7.2 9 13
Rated output current (A)
(light load)
3.1 5.1 7.2 9 13 17
Output voltage Three‑phase 0 V to input voltage
Max. output frequency 599 Hz (editable through a parameter)
Carrier frequency
0.8 kHz to 8.0 kHz (automatically adjusted according to the load
characteristics)
Overload capacity
Heavy load (G‑type AC drive): 150% for 60s with rated current
Light load (P‑type AC drive): 110% for 60s with rated current
Input
Rated input current (A)
(heavy load)
2.4 4.6 6.3 9 11.4 16.7
Rated input current (A) (light
load)
3.7 6.4 9.1 11.3 15.9 22.4
Rated voltage/frequency Three‑phase 200 VAC to 240 VAC, 50/60 Hz
Voltage range
Allowable fluctuation: –15% to +10% (170 VAC to 264 VAC)
Frequency range
Allowable fluctuation: ±5% (47.5 Hz to 63 Hz)
Power capacity (kVA) (heavy
load)
1.1 2.1 2.9 4.1 5.2 7.6
Power capacity (kVA) (light
load)
1.7 2.9 4.2 5.2 7.3 10.2
Thermal
design
Thermal design power (kW)
(heavy load)
0.046 0.068 0.081 0.109 0.138 0.201
Thermal design power (kW)
(light load)
0.06 0.088 0.112 0.14 0.207 0.273
Air flow (CFM)
‑ 9 9 9 20 24
Overvoltage category
OVC III
Pollution degree
PD2
IP rating
IP20