Figure 5‑18 Dimension drawing of T6 models (with conduit box)
5.3 Cables
5.3.1 Main Circuit Cable
Power cable selection requirements
Observe national or regional regulations and the following requirements when
selecting power cables.
● Compliant with EN 60204‑1 and IEC 60364‑5‑52 standards
● PVC cables with copper conductors
● 40°C ambient temperature and 70°C cable surface temperature (Note: Contact
Inovance for ambient temperatures above 40°C.)
● Symmetrical cables with copper‑braided shield
If the recommended cables for peripheral equipment or options are not suitable for
the product, contact Inovance.