Options
74
Structure Model
Fuse
(Bussmann)
Contactor Circuit Breaker
Rated Current (A)
Model
Rated Current (A) Rated Current (A)
T11
MD500‑2T132G/160P‑PLUS
800 FWH‑800A 475 630
T12
MD500‑2T160G/200P‑PLUS
1000 170M5016 620 800
MD500‑2T200G/220P‑PLUS
1400 170M6017 800 1000
Table 5–14 Recommended specifications of fuses, contactors, and circuit breakers
(single‑phase 200 V to 240 V)
Structure Model
Fuse
(Bussmann)
Contactor Circuit Breaker
Rated Current
(A)
Model
Rated Current
(A)
Rated Current (A)
T2
MD500‑2S0.4GB‑PLUS 10 FWP‑10B 9 10
MD500‑2S0.7GB‑PLUS 15 FWP‑15B 12 13
MD500‑2S1.5GB‑PLUS 20 FWP‑20B 16 16
MD500‑2S2.2GB‑PLUS 30 FWP‑30B 30 32
Note
See "Requirements on Protective Devices" in section UL/cUL Certification" for require‑
ments on fuses and circuit breakers of UL‑compliant drives.
5.4.2 AC Input Reactor
An AC input reactor is used to eliminate harmonics in the input current. As an
optional device, the reactor can be installed externally for suppressing harmonics
where necessary.
To install an AC input reactor on models above 200 kW, ensure sufficient space is
reserved in the cabinet for installing the reactor.
Models and dimensions of Inovance AC input reactors
Recommended models are listed in the following tables.