Options
‑67‑
Table 5–6 Recommended cable specifications (three‑phase 200 V to 240 V)
Structure Model
RST/UVW
Grounding Cable
Screw
Cable (mm
2
)
[1]
Cable Lug
Model
Cable
(mm
2
)
[1]
Cable Lug
Model
T1
MD500‑2T0.4G/0.7PB‑PLUS
3 x 0.75 TNR0.75‑4 0.75 TNR0.75‑4 M4
MD500‑2T0.7G/1.1PB‑PLUS
MD500‑2T1.1G/1.5PB‑PLUS
MD500‑2T1.5G/2.2PB‑PLUS
3 x 1 TNR1.25‑4 1 TNR1.25‑4 M4
T2
MD500‑2T2.2G/3.7PB‑PLUS
3 x 1.5 TNR1.25‑4 1.5 TNR1.25‑4 M4
MD500‑2T3.7G/5.5PB‑PLUS
3 x 2.5 TNR2‑4 2.5 TNR2‑4 M4
T3
MD500‑2T5.5G/7.5PB‑PLUS
3 x 6 TNR5.5‑5 6 TNR5.5‑5 M5
T4
MD500‑2T7.5G/11PB‑PLUS
3 x 10 TNR8‑5 10 TNR8‑5 M5
T5
MD500‑2T11G/15P(B)‑PLUS
3 x 16 GTNR16‑6 16 GTNR16‑6 M6
T6
MD500‑2T15G/18.5P(B)‑PLUS
3 x 16 GTNR16‑6 16 GTNR16‑6 M6
MD500‑2T18.5G/22P(B)‑PLUS
3 x 25 GTNR25‑6 16 GTNR16‑6 M6
T7
MD500‑2T22G/30P(B)‑PLUS
3 x 35 GTNR35‑8 16 GTNR16‑8 M8
MD500‑2T30G/37P(B)‑PLUS
3 x 50 GTNR50‑8 25 GTNR25‑8 M8
T8
MD500‑2T37G/45P(B)‑PLUS
3 x 70 GTNR70‑12 35 GTNR35‑12 M12
MD500‑2T45G/55P‑PLUS
3 x 95 GTNR95‑12 50 GTNR50‑12 M12
MD500‑2T55G/75P‑PLUS
3 x 120 GTNR120‑12 70 GTNR70‑12 M12
T9
MD500‑2T75G/90P‑PLUS 2 x (3 x 95)
BC95‑12 95 BC95‑12 M12
T10
MD500‑2T90G/110P‑PLUS 2 x (3 x 120)
BC120‑12 120 BC120‑12 M12
MD500‑2T110G/132P‑PLUS 2 x (3 x 150)
BC150‑12 150 BC150‑12 M12
T11
MD500‑2T132G/160P‑PLUS 2 x (3 x 185)
BC185‑16 185 BC185‑16 M16
T12
MD500‑2T160G/200P‑PLUS 2 x (3 x 240)
BC240‑16 240 BC240‑16 M16
MD500‑2T200G/220P‑PLUS 2 x (3 x 240)
BC240‑16 240 BC240‑16 M16
Table 5–7 Recommended cable specifications (single‑phase 200 V to 240 V)
Structure Model
RST/UVW
Grounding Cable
Screw
Cable
(mm
2
)
[1]
Cable Lug
Model
Cable
(mm
2
)
[1]
Cable Lug
Model
T2
MD500‑2S0.4GB‑PLUS 0.75 TNR0.75‑4 0.75 TNR8‑5
M4
MD500‑2S0.7GB‑PLUS 1.5 TNR0.75‑4 1.5 TNR8‑5
MD500‑2S1.5GB‑PLUS 2.5 TNR1.25‑4 1.5 TNR8‑5
MD500‑2S2.2GB‑PLUS 4.0 TNR2‑4 2.5 TNR8‑5