To meet requirements of EN 61800‑5‑1 and UL61800‑5‑1, install a fuse and circuit
breaker on the input side to prevent accidents caused by internal short circuit.
The following tables list recommended fuses and circuit breakers made by Bussmann.
Table 5–12 Recommended specifications of fuses, contactors, and circuit breakers
(three‑phase 380 V to 480 V)
Structure Model
Fuse
(Bussmann, and UL‑compliant)
Contactor Circuit Breaker
Rated Current (A)
Model
Rated Current (A) Rated Current (A)
T1
MD500T0.4G/0.7PB‑PLUS
5 FWP‑5B 9 4
MD500T0.7G/1.1PB‑PLUS
10 FWP‑10B 9 6
MD500T1.1G/1.5PB‑PLUS
10 FWP‑10B 9 6
MD500T1.5G/2.2PB‑PLUS
10 FWP‑10B 9 10
MD500T2.2G/3PB‑PLUS
15 FWP‑15B 12 13
MD500T3.0G/3.7PB‑PLUS
20 FWP‑20B 16 16
T2
MD500T3.7G/5.5PB‑PLUS
30 FWP‑30B 26 25
MD500T5.5G/7.5PB‑PLUS
40 FWP‑40B 26 32
T3
MD500T7.5G/11PB‑PLUS
60 FWP‑60B 38 50
MD500T11G/15PB‑PLUS
70 FWP‑70B 50 63
T4
MD500T15G/18.5PB‑PLUS
70 FWH‑70B 50 63
T5
MD500T18.5G/22P(B)‑PLUS
MD500T18.5G/22P(B)‑T‑
PLUS
100 FWH‑100B 65 80
MD500T22G/30P(B)‑PLUS
MD500T22G/30P(B)‑T‑PLUS
125 FWH‑125B 80 80
T6
MD500T30G/37P(B)‑PLUS
125 FWH‑125B 80 100
MD500T37G/45P(B)‑PLUS
150 FWH‑150B 95 160
T7
MD500T45G/55P(B)‑PLUS
200 FWH‑200B 115 160
MD500T55G/75P(B)‑PLUS
250 FWH‑250A 150 250
T8
MD500T75G/90P(B)‑PLUS
275 FWH‑275A 170 250
MD500T90G/110P‑PLUS
325 FWH‑325A 205 250
MD500T110G/132P‑PLUS
400 FWH‑400A 245 400
T9
MD500T132G/160P‑PLUS
500 FWH‑500A 300 400
MD500T160G/200P‑PLUS
600 FWH‑600A 410 500
T10
MD500T200G/250P‑PLUS
MD500T200G/250P‑L‑PLUS
800 FWH‑800A 475 630
MD500T220G/280P‑PLUS
MD500T220G/280P‑L‑PLUS
800 FWH‑800A 620 800
T11
MD500T250G/315P‑PLUS
MD500T250G/315P‑L‑PLUS
1000 170M5016 620 800
MD500T280G/355P‑PLUS
MD500T280G/355P‑L‑PLUS
1000 170M5016 620 800