Installation
‑71‑
Type
Mark
Name
Function Description
Digital input
DI1‑OP
Digital input 1 Photocoupler isolation and
bipolar input
Input impedance: 1.72 kΩ
Voltage range for effective level
input: 9 V to 30 V
DI2‑OP
Digital input 2
DI3‑OP
Digital input 3
DI4‑OP
Digital input 4
DI5‑OP
Digital input 5 Besides features of DI1 to DI4, DI5
can also be used for high‑speed
pulse input.
Input impedance: 1.16 kΩ
Maximum input frequency: 100
kHz
Operating voltage range: 15 V to
30 V
Analog output
AO1‑GND
Analog output
1
The DIP switch on the control
board is used to determine
voltage output (default) or current
output.
Output voltage range: 0–10 V
Output current range: 0–20 mA
Digital output
DO1‑CME
Digital output
1
Photocoupler isolation and
bipolar open collector output
Output voltage range: 0–24 V
Output current range: 0–50 mA
Note that CME and COM are
internally insulated, but are
shorted externally by jumper as
the factory settings. In this case,
DO1 is driven by +24V. To drive
DO1 by external power supply,
remove the jumper between CME
and COM.
FM‑COM
High‑speed
pulse output
The terminal is set by F5‑00 (FM
terminal output selection). When
the terminal is used for high‑
speed pulse output, the maximum
frequency is 100 kHz. When the
terminal is used for collector open
output, it has the same
specifications as DO1.
Relay output T/A
Common
terminal
Contact driving capacity:
250 VAC, 3 A, COSø = 0.4
30 VDC, 1 A
T/B Normally
closed
terminal
T/C Normally
open terminal