Intergas XTREME 24 - Parameters

Intergas XTREME 24
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
Para
metre
Setting
Set
value Description/Setting range
P001
System type 0
0 = Xtreme Kombi
1 = Xtreme Solo + Boiler
2 = Xtreme Tap
3 = Xtreme Solo
P010
Set maximum central heating output
75
-------
100
75 = Xtreme 36
100 = Xtreme 24 / Xtreme 30
25% to 100% (see §8.5)
P030
Central heating pump setting 0
0 = overrun active
1 = continuous
1
P031
Maximum capacity of modulating central
heating pump
65 Set value of parameter P032 to 100%
P032
Minimum capacity of modulating central
heating pump
35 15% to set value of parameter P031
P033
Central heating pump overrun aer central
heating demand
1 0 to 15 minutes
P034
Central heating pump overrun aer boiler
operation
1 0 to 15 minutes (n/a for Kombi boiler)
P035
Step modulation 1
0 = o
1 = on
P036
Anti-pendulum time central heating 5
Minimum switch-o time for boiler water temperature
0 to 15 minutes
p040
Activate clock program CH operation 0
0 = inactive
1 = active
P057
Response of OpenTherm room thermostat 1
0 = do not respond to heat demand if requested
temperature is lower than 30°C
1 = respond to heat demand with minimum flow
temperature limited at 30°C
2 = respond to heat demand with maximum set flow
temperature (on/o function)
P059
Maximum setting value of flow temperature 80 10°C to 90°C
P070
Set maximum DHW capacity 100 20% to 100%
P074
Number ECO days 7 0 to 10 days
P075
Control temperature during boiler operation 80 60°C to 90°C
P077
Waiting time central heating demand aer
DHW operation
0 to 15 minutes
P081
Setting of three-way valve or electric shut-
o valve
0
0 = powered during central heating demand
1 = powered during DHW operation
p087
Activate clock program DHW operation 0
0 = inactive
1 = active
8.3 Parameters