Parameter Access Tables
www.invertekdrives.com
Optidrive P2 Advanced User Guide Revision 2.00
4.7.6. Group 6 : Advanced Parameter set (Level 3)
Parameter
Number
R/W
Modbus
RTU
Register
Number
CAN
Open
Index
CAN
Open
Sub
Index
Profibus
DP
DeviceNet
EtherNet
IP
EtherCAT
Modbus
TCP
Profinet
IO
Parameter Name
Setting Range
Scaling
Type
P6-01
R/W
601
2259h
0h
2, 90
A2h, 601, X
A2h, 601, X
2259h
1128
0, 0, 1, 0259h
Firmware Upgrade enable
0: Disabled
1: Enable (IO and DSP)
2: Enable (IO only)
3: Enable (DSP only)
U16
P6-02
R/W
602
225Ah
0h
2, 91
A2h, 602, X
A2h, 602, X
225Ah
1129
0, 0, 1, 025Ah
Auto thermal management
0: Disable
1: Enable
WORD
P6-03
R/W
603
225Bh
0h
2, 92
A2h, 603, X
A2h, 603, X
225Bh
1130
0, 0, 1, 025Bh
Auto-reset delay time
1 to 60
U16
P6-04
R/W
604
225Ch
0h
2, 93
A2h, 604, X
A2h, 604, X
225Ch
1131
0, 0, 1, 025Ch
User relay hysteresis band
0 - 250
1 = 0.1%
U16
P6-05
R/W
605
225Dh
0h
2, 94
A2h, 605, X
A2h, 605, X
225Dh
1132
0, 0, 1, 025Dh
Encoder feedback enable
0: Disabled
1: Enable
WORD
P6-06
R/W
606
225Eh
0h
2, 95
A2h, 606, X
A2h, 606, X
225Eh
1133
0, 0, 1, 025Eh
Encoder PPR
0 to 65535
U16
P6-07
R/W
607
225Fh
0h
2, 96
A2h, 607, X
A2h, 607, X
225Fh
1134
0, 0, 1, 025Fh
Speed error trip level
0 to 500
1 = 0.1%
U16
P6-08
R/W
608
2260h
0h
2, 97
A2h, 608, X
A2h, 608, X
2260h
1135
0, 0, 1, 0260h
Max speed ref frequency
0, 5 to 20
U16
P6-09
R/W
609
2261h
0h
2, 98
A2h, 609, X
A2h, 609, X
2261h
1136
0, 0, 1, 0261h
Speed Droop Control
0 to 250
1 = 0.1%
U16
P6-10
R/W
610
2262h
0h
2, 99
A2h, 610, X
A2h, 610, X
2262h
1137
0, 0, 1, 0262h
Enable Function Block Program operation
0: Disable
1: Enable
WORD
P6-11
R/W
611
2263h
0h
2, 100
A2h, 611, X
A2h, 611, X
2263h
1138
0, 0, 1, 0263h
Speed hold time on enable
0 to 2500
1 = 0.1s
U16
P6-12
R/W
612
2264h
0h
2, 101
A2h, 612, X
A2h, 612, X
2264h
1139
0, 0, 1, 0264h
Speed hold time on disable
0 to 2500
1 = 0.1s
U16
P6-13
R/W
613
2265h
0h
2, 102
A2h, 613, X
A2h, 613, X
2265h
1140
0, 0, 1, 0265h
Hoist mode brake release delay
0 to 50
1 = 0.1s
U16
P6-14
R/W
614
2266h
0h
2, 103
A2h, 614, X
A2h, 614, X
2266h
1141
0, 0, 1, 0266h
Hoist mode brake apply delay
0 to 50
1 = 0.1s
U16
P6-15
R/W
615
2267h
0h
2, 104
A2h, 615, X
A2h, 615, X
2267h
1142
0, 0, 1, 0267h
Torque threshold for hoist brake release
0 to 2000
1 = 0.1%
U16
P6-16
R/W
616
2268h
0h
2, 105
A2h, 616, X
A2h, 616, X
2268h
1143
0, 0, 1, 0268h
Torque threshold timeout
0 to 250
1 = 0.1s
U16
P6-17
R/W
617
2269h
0h
2, 106
A2h, 617, X
A2h, 617, X
2269h
1144
0, 0, 1, 0269h
Max Torque limit timeout
0 to 250
1 = 0.1s
U16
P6-18
R/W
618
226Ah
0h
2, 107
A2h, 618, X
A2h, 618, X
226Ah
1145
0, 0, 1, 026Ah
DC injection braking voltage
0 : Auto
0 to 250
0 = Auto
1= 0.1%
U16
P6-19
R/W
619
226Bh
0h
2, 108
A2h, 619, X
A2h, 619, X
226Bh
1146
0, 0, 1, 026Bh
Brake resistor value
0, Min value to 200
1 = 1
U16
P6-20
R/W
620
226Ch
0h
2, 109
A2h, 620, X
A2h, 620, X
226Ch
1147
0, 0, 1, 026Ch
Brake resistor power
0 to 20000
1= 0.01kw
U16
P6-21
R/W
621
226Dh
0h
2, 110
A2h, 621, X
A2h, 621, X
226Dh
1148
0, 0, 1, 026Dh
Brake chopper UT duty cycle
0 to 200
1 = 0.1%
U16
P6-22
R/W
622
226Eh
0h
2, 111
A2h, 622, X
A2h, 622, X
226Eh
1149
0, 0, 1, 026Eh
Reset cooling fan run-time
0: Disable
1: Enable
WORD
P6-23
R/W
623
226Fh
0h
2, 112
A2h, 623, X
A2h, 623, X
226Fh
1150
0, 0, 1, 026Fh
Reset kWh meter
0: Disable
1: Enable
WORD
P6-24
R/W
624
2270h
0h
2, 113
A2h, 624, X
A2h, 624, X
2270h
1151
0, 0, 1, 0270h
Service time interval
0 … 60 000 h
(0 = disabled)
1=1
U16
P6-25
R/W
625
2271h
0h
2, 114
A2h, 625, X
A2h, 625, X
2271h
1152
0, 0, 1, 0271h
Reset service indicator
0: Disable
1: Reset
1=1
WORD
P6-26
R/W
626
2272h
0h
2, 115
A2h, 626, X
A2h, 626, X
2272h
1153
0, 0, 1, 0272h
Analog output 1 scaling
0 to 5000
1 = 0.1
U16
P6-27
R/W
627
2273h
0h
2, 116
A2h, 627, X
A2h, 627, X
2273h
1154
0, 0, 1, 0273h
Analog output 1 offset
-5000 to 5000
1 = 0.1%
S16
P6-28
R/W
628
2274h
0h
2, 117
A2h, 628, X
A2h, 628, X
2274h
1155
0, 0, 1, 0274h
P0-80 display value index
0 to 127
U16
P6-29
R/W
629
2275h
0h
2, 118
A2h, 629, X
A2h, 629, X
2275h
1156
0, 0, 1, 0275h
Save User Parameters as default
0: Disable
1: Enable
WORD
P6-30
R/W
630
2276h
0h
2, 119
A2h, 630, X
A2h, 630, X
2276h
1157
0, 0, 1, 0276h
Level 3 access code
0 to 9999
U16