Goodrive170-PV Series Solar Pump Inverter Function parameter list
-38-
system becomes stable.
Note: This parameter is invalid when
terminal function 43 is valid.
Vmpp
voltage
given
through
keypad
0.0–6553.5Vdc
When P15.01 is 0, this parameter
determines the reference voltage. (During
testing, the reference voltage value must
be less than the PV input voltage.
Otherwise, the system runs at the lower
limit of frequency.)
PID control
deviation
limit
0.0–100.0% (100.0% corresponding to
P15.02)
PI adjustment is performed only when the
ratio of the difference between the actual
voltage and reference voltage to the
reference voltage, which is abs (Actual
voltage – Reference voltage) * 100.0% /
(Reference voltage), exceeds P15.03. The
default value is 0.0%.
abs: The absolute value is used.
PID output
upper limit
frequency
P15.05–100.0% (100.0% corresponding to
P00.03)
P15.04 is used to limit the Max. value of
target frequency.
100.0% corresponds to P00.03.
After PI adjustment, the target frequency
cannot exceed the upper limit.
PID output
lower limit
frequency
0.0%–P15.04 (100.0% corresponding to
P00.03)
P15.05 is used to limit the Min. value of
target frequency.
100.0% corresponds to P00.03.
After PI adjustment, the target frequency
cannot be less than the lower limit.