Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-147-
Starting
frequency point
for switching off
IF mode for
asynchronous
motor 1
Enable/disable
IF mode of
asynchronous
motor 2
IF current setting
of asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the output
current. The value is a percentage in relative to
the rated current of the motor.
Setting range: 0.0–200.0%
IF proportional
coefficient of
asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the
proportional coefficient of the output current
closed-loop control.
Setting range: 0–5000
IF integral
coefficient of
asynchronous
motor 2
When IF control is adopted for asynchronous
motor 2, this parameter is used to set the
integral coefficient of the output current
closed-loop control.
Setting range: 0–5000
Starting
frequency point
for switching off
IF mode for
asynchronous
motor 2
End frequency
point for
switching off IF
mode for
asynchronous
motor 1
End frequency
point for
switching off IF
mode for
asynchronous
motor 2