Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-240-
Function
code
Name
Description
Default
value
Modify
P91.02
Zero speed
offset
0.050.0%
2.0%
P91.03
Upper-limit
frequency
source of torque
control
03
0: P03.14, P03.15
1: Forward rotation limit set by line speed
2: Reverse rotation limit set by line speed
3: Forward and reverse rotations limit set by line
speed
3
P91.04
Running
frequency upper
limit offset of
tension control
0.0100.0%
5.0%
P91.05
Differential
separation
threshold
0.0100.0%
5.0%
P91.06
PID restricts
reverse limit at
zero speed
01
0: Enable
1: Disable
0
P91.07
Torque
compensation
selection
0x0000x111
Ones place: Frictional torque compensation
0: No
1: Yes
Tens place: Inertia compensation
0: No
1: Yes
Hundreds place: Compensation direction
0: In line with torque direction
1: Different from torque direction
0x000
P91.08
System
mechanical
parameters
identification
02
0: No operation
1: Enable system mechanical inertia
identification
2: Enable mechanical friction torque
identification
0
P91.09
Static friction
torque
compensation
coefficient
0.0100.0%
0.0%
P91.10
Sliding friction
torque
compensation
coefficient 1
0.0100.0%
0.0%
P91.11
Sliding friction
torque
compensation
coefficient 2
0.0100.0%
0.0%

Table of Contents