Basic Operation
measurement accuracy. (Refer to 2.4 Connecting the Device Under Test
(DUT))
The procedures to set the menu item are as follows.
1. Press the composite keys [Shift]+[P-set] (System) on the front panel to en-
ter the system menu.
2. Press the Up/Down key or turn the knob to select the Sense and press
[Enter].
3. Press the Left / Right key or turn the knob to adjust the value of this
parameter.
• Off: Default value, indicates turn the sense function off.
• On: Indicates turn the sense function on.
4. After the parameter settings are complete, press [Enter].
6.8 Select Trigger Source (Trig Source)
For the IT6000B series power system, the List and data logging functions can
be triggered for running by the following methods:
• Manual: Default value, indicates the trigger occurs when the
[Shift]+[On/Off] (Trigger) keys are pressed from the front panel.
• Bus: Indicates the trigger occurs via the communication cables. When the
trigger command *TRG is received, the IT6000B instrument generates a
trigger.
• External: Indicates the trigger occurs via the pin 4 of the digital I/O interface
(P-IO).
For details, see 6.11.4 IO–4. Ext-Trig, Not-Invert.
The List function and the data logging function have the same steps for select-
ing the trigger source. They need to be set separately in different menu items
(ListTrig Source and DLogTrig Source). Therefore, this section takes the List
trigger source setting as an example to introduce the operation steps.
1. Press the composite keys [Shift]+[P-set] (System) on the front panel to en-
ter the system menu.
2. Press the Up/Down key or turn the knob to select the ListTrig Source and
press [Enter].