Mobile Mode
Extended Alarm Flag
This is retrievable with two-way communication.
Register Error Flag
■
The Register Error flag sets if the Register Error Detected flag is active for 24 hours.
■
The Register Error Flag remains active for 40 days in mobile mode.
Register Error Detected
■
Register Error Detected indicates that the 500WERTModule is not communicating with
the register/meter. The event or alarm flag automatically clears after the
500WERTModule receives a successful read from the register.
Note: The Register Error Detected flag may be an indicator of a damaged register.
Low Battery Warning
■
The remote modules include a battery life estimator. The estimator is based on the
number of data packets sent at the various power levels and the age (self-discharge) of
the 500WERTModule . The low battery warning allows the utility to easily identify which
500WERTModules are nearing end-of-life in a mixed population and gives the utility the
opportunity to schedule replacement.
Note: The low battery warning is a single flag that is set when the battery has less than 10% remaining
capacity, which typically corresponds to two years of battery life remaining. Battery life is evaluated daily at
midnight.
Network Mode
Note: 500WERTModule events and alarms are dependent on the module's firmware version. For more
information, see Firmware Functionality on page 11.
The 500WERTModule reports the tampers available in mobile mode as well as extended
meter alarms available from new solid-state and electronic meters connected to the
500WERTModule. The extended alarms include:
■
Empty pipe
■
Temperature
■
High flow
■
Meter low battery
■
Meter tampering
■
Reverse flow
■
Zero consumption
Gen5 500WERTModule Remote Installation Guide 1 Introduction
December 5, 2022 LDI-0343 REV002 Itron, Inc. Page 10 of 48