EasyManua.ls Logo

janitza UMG96L - Page 27

janitza UMG96L
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 27
These specifications presuppose a yearly calibration and a warm up time of 10 minutes.
Used abbreviations:
rng = of measuring range
rdg = of measured value
1)
Measuring range with scale factor = 1, (Current tranformer = 5/5A, 1/1A)
2
) In the range of -10..18°C and 28..55°C, an additional error of +-0,5‰ of measured value has to
be considered per K.
3
) If the measured apparent power is in the range of 1% .. 100% of the measuring range, cos(phi)
is indicated with an accuracy of +-3%.
4)
Accuracy class according to DIN EN61036:2001-01, VDE0418part 7, IEC61036:1996 + A1:2000
5)
The auxiliary voltage is taken from the measuring voltage.
6)
The maximum indication range and the resolution of real and reactive energy depends on
Transformer ratio v = vi * vu.
vi = Transformer ratio of current transformer.
vu = Transformer ratio of voltage transformer.
Example: 200/5A -> vi = 40
1000/100V -> vu = 10
v = vi * vu
v = 40 *10
v = 400
1 10 100 400 v
999.999.999
210.000.000
21.000.000,0
2.100.000,00
Energy
/kvarh /kWh
Transformer ratio v
Indication range and resolution for
real and reactive energy

Related product manuals