Configuration data
Description Display Setting range Presettings
Current transf., primary CT 1A .. 10,0kA 5A
Current transf., secondary CT 1A, 5A 5A
Voltage transf., primary
Type plate, 196 .. 255V VT 100V .. 60.0kV 400V
Type plate, 90 .. 160V VT 100V .. 60.0kV 200V
Type plate, 45 .. 80V VT 100V .. 60.0kV 100V
Voltage transformer, sec.
Type plate, 196.. 255V VT 400V (not changeable) 400V
Type plate, 90 .. 160V VT 200V, 220V 200V
Type plate, 45 .. 80V VT 100V, 110V 100V
Averaging time, current 5, 10, .. 900Sec. 900Sec.
Averaging time, power 5, 10, .. 900Sec. 900Sec.
Measured value rotation 0 .. 250seconds 0 = no rotation
Measured value selection All indications all indications
LCD contrast 0 .. 7 3
Software Release not changeable x.xx
User passwort 000 .. 999 ā€ž000ā€œ = no password
Working hours counter not changeable 0h