Declaration of conformity
The UMG96L fulfills the protection guidelines of:
Guideline 89/336/EWG in combination with DIN EN61326 (2002-03) as well as
Guideline 73/23/EWG and 93/68/EWG in combination with EN 61010-1 (2002-08)
Safety guidelines
Safety requirements for electrical equipment for measurement, control, and laboratory use
Part1: General requirements : EN61010-1:2001, IEC 61010-1:2001
Test voltage
Enclosure against measuring inputs : 2kV AC
Between the inputs for measuring and auxiliary voltage and the current inputs exists a functional
separation of 2000V AC.
EMC requirements
Electromagnetic emission : DIN EN61326:2002-03, table 4, class B
Electromagnetic immunity : DIN EN61326:2002-03, table A.1
Enclosure : ESD test, IEC61000-4-2:2001 (4kV/8kV)
: Electromagnetic RF-field, IEC61000-4-3:2002 (10V/m)
: Netfrequent magnetic field, IEC61000-4-8:2000 (120A/m)
AC-power line : AC-Power variation and dropout, IEC61000-4-11:2000
: Fast transients (Burst), IEC61000-4-4:2001 (2kV)
: Powerful pulse (Surge), IEC61000-4-5:2000 (1kV L- N)
: RF induced on lines, IEC61000-4-6:2000 (3V)
Current transformer inputs : Fast transients (Burst), IEC61000-4-4:2001 (2kV)
: Powerful pulse (Surge), IEC61000-4-5:2000 (1kV)
: RF induced on lines, IEC61000-4-6:2000 (3V)