EasyManua.ls Logo

Johnson Controls FX-PCG26 - Page 22

Johnson Controls FX-PCG26
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 4: FX-PCG2511 and FX-PCG26 terminal blocks, functions, ratings, requirements, and
cables
Terminal block
label
Terminal
label
Function, ratings,
requirements
Determine wire size and
maximum cable length
Analog Output - Voltage
Mode (0–10 VDC)
10 VDC maximum output
voltage
10 mA maximum output
current
Required an external load of
1,000 ohms or more.
See Guideline A in Table 5.OUTn
Binary Output - 24 VAC Triac
(External Power Source only)
Connects OUTn to OCOMn
when activated.
External Power Source
Requirements:
30 VAC maximum output
voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
See Guideline C in Table 5.
Analog Output Signal
Common All Configurable
Outputs (COs) defined as
Analog Outputs (AOs) are
isolated from all other
commons except the Binary
Input common.
CONFIGURABLE
(Outputs)
OCOMn
Binary Output Signal
Common All Configurable
Outputs (COs) defined as
Binary Outputs are isolated
from all other commons,
including other CO commons.
Same as (Configurable) OUTn.
FX-PCG26 General Purpose Programmable Controller Installation Instructions22