Johnson Controls
Start-Up & Operation Guide | 5586996-JSG-A-0120
51
Operation
Modulating HGRH
3-Way Stepper
Valve
LD20880
Figure 22: HGRH Schematic
Economizer
The rooftop unit can have a factory installed econo-
mizer as an option.
Economizer operation is often referred to as free cool-
ing because it uses outside air instead of mechanical
cooling to satisfy the cooling demands when the out-
side air conditions are suitable.
NOTE: There is a difference between economizer op-
eration and ventilation operation.
Ventilation operation is active when the unit
mode is OCC and the supply fan is operating
when a ventilation option is installed
Economizer operation is only active when
there is a demand for cooling and the out-
side air conditions are suitable for meeting
the demands utilizing outdoor air
Ventilation and economizer options both use
the outside air damper in their respective se-
quences
There are four economizer options that can be in-
stalled: dry bulb, singly enthalpy, dual enthalpy, and
differential dry bulb.
Changeover Method
The unit can be ordered with one of the three econo-
mizer options:
Dry Bulb: Measures the dry bulb temperature of
the outside air to determine if conditions are suit-
able for economizer operation
Single Enthalpy: Measures the outside air en-
thalpy (temperature and humidity) to determine if
conditions are suitable for economizer operation
Dual Enthalpy: Measures the outside air enthal-
py against the return air enthalpy to determine if
conditions are suitable for economizer operation
There are also two options that can be selected in the
unit setup.
Differential Dry Bulb: Measures the dry bulb
temperature of the outside air against the dry bulb
temperature of the space
Auto: The unit controller checks to see what
sensors are installed and reliable and determine
which of the four methods are available to use for
economizer operation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls GVB Series and is the answer not in the manual?

Johnson Controls GVB Series Specifications

General IconGeneral
BrandJohnson Controls
ModelGVB Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals